7-9
7 Tag Data Link Functions
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User’s Manual (W563)
7-
1 Int
rod
uctio
n
t
o
T
ag D
at
a L
inks
7
7-1
-5 S
tarting and
S
topping T
ag Dat
a Links
Additional Information
•
To calculate the number of connections of each connection type, refer to
•
If the maximum number of connections is exceeded, you must review the number of connec-
tions for the built-in EtherNet/IP port, or the number of nodes. When you use an NJ-series
CPU Unit, you can also consider adding EtherNet/IP Units.
Tag data links are automatically started when the data link parameters are downloaded from the Net-
work Configurator and the power supply to the NY-series Controller is turned ON. Thereafter, you can
start and stop tag data links for the entire network or individual devices from the Network Configurator.
Starting and stopping tag data links for individual devices must be performed for the originator. Further-
more, you can use system-defined variables to start and stop the entire network. Refer to
ing and Stopping Tag Data Links
for details.
You can include the Controller status as a member of a tag set in the data sent and received. The Con-
troller status is a set of flags that indicate the operating status of the Controller (operating information,
error information, Controller error level). If the Controller status is specified as an output (send) tag, the
Controller status is added to the start of the tag set in the following format. (Select the
Include
Option
for the
Controller Status
in the upper right of the Edit Tag Set Dialog Box.)
* Of the flags in bits 5 to 7 that indicate the current error level, only the flag for the highest error level changes to
TRUE. For example, if a minor fault level Controller error and a major fault level Controller error occur at the
same time, only the flag for the major fault level Controller error (bit 7) will change to TRUE and the flag for the
minor fault level Controller error (bit 5) will remain FALSE.
To receive the Controller status, specify the Controller status for the In - Consume Tab Page in the dia-
log box used to edit the receive tag set. (Select the
Include
Option for the
Controller Status
in the upper
right of the Edit Tag Set Dialog Box.) When a tag data link is started, the contents of the Controller sta-
tus is stored in the system variables that are given below.
•
Target PLC Operating Mode
•
Target PLC Error Information
7-1-5
Starting and Stopping Tag Data Links
7-1-6
Controller Status
_EIP_TargetPLCModeSta
_EIP_TargetPLCErr
15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
0 0 0 0 0 0 0 0 0 0 0
Major fault level
Controller error
Partial fault level Controller error
Minor fault level
Controller error
Controller Error Flag
Controller Operating Flag