2 Installing Ethernet Networks
2-8
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User’s Manual (W563)
Between two Ethernet switches
Regardless of which baud rate is used, check with the Ethernet switch manufacturers for information
about installing the network between Ethernet switches, and in particular whether or not it is neces-
sary to connect the cable shields to the connector hoods.
•
Press the cable connector in firmly until it locks into place at both the Ethernet switch and the built-in
EtherNet/IP port.
•
Do not lay the twisted-pair cable together with high-voltage lines.
•
Do not lay the twisted-pair cable near devices that generate noise.
•
Do not lay the twisted-pair cable in locations subject to high temperatures or high humidity.
•
Do not lay the twisted-pair cable in locations subject to excessive dirt and dust or to oil mist or other
contaminants.
If you connect a shielded cable with only the Ethernet switch side connected to the connector hood, you
must attach a clamp core on the built-in EtherNet/IP port side. The recommended clamp core and
attachment method are given below.
Recommended clamp core
ESD-SR-250 dimensions
Recommended attachment method
(1) Attaching a clamp core to a communications cable
(2) Attaching a communications cable
Other Precautions When Laying the Twisted-pair Cable
Recommended Clamp Core and Attachment Method
Manufacturer
Product
Model
NEC TOKIN
Clamp core
ESD-SR-250
31.5
38.0
31.6
13 dia. max.
Make two loops with the cable
as shown.
Attach close to the cable
connection as shown.
Built-in
EtherNet/IP
port on
NY-series
Controller