14 Checking Communications Status of Network and Troubleshooting
14-10
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User’s Manual (W563)
01
0108
Error code returned from target:
Attempted to open a connection with
an unsupported connection type.
This error does not
occur.
Check which connec-
tion types can be used
by the target. (Contact
the manufacturer.) Only
multicast and point-to-
point connections can
be set.
Check which connec-
tion types can be used
by the originator. (An
error will occur if a con-
nection other than a
multicast or point-to-
point connection is set.)
01
0109
Error code returned from target:
The connection size settings are dif-
ferent in the originator and target.
Check the connection sizes set in the originator and target.
01
0110
Error code returned from target:
The target was unable to open the
connection, because of its operating
status, such as downloading set-
tings.
Check whether the
tag data link is
stopped at the tar-
get. (Restart the tag
data link communi-
cations with the soft-
ware switch.)
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufacturer.)
Check whether the tag
data link is stopped at
the target. (Restart the
tag data link communi-
cations with the soft-
ware switch.)
01
0111
Error code returned from target:
The RPI was set to a value that
exceeds the specifications.
This error does not
occur.
Check the target’s RPI
setting specifications.
Set the originator’s RPI
setting to 10 seconds
or less.
01
0113
Error code generated by originator
or returned from target:
Attempted to open more connec-
tions than allowed by the specifica-
tions (32).
Check the connec-
tion settings (number
of connections) at
the originator and
target.
Check the connection
settings (number of
connections) at the
originator and target.
Check the connection
specifications for
devices from other
manufacturers.
Check the connection
settings (number of
connections) at the
originator and target.
Check the connection
specifications for
devices from other
manufacturers.
01
0114
Error code returned from target:
The Vendor ID and Product Code
did not match when opening con-
nection.
This error does not
occur.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.) Check that the
target device’s EDS file
is correct.
Check the originator’s
connection settings.
01
0115
Error code returned from target:
The Product Type did not match
when opening connection.
This error does not
occur.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.) Check that the
target device’s EDS file
is correct.
Check the originator’s
connection settings.
01
0116
Error code returned from target:
The Major/Minor Revisions did not
match when opening connection.
Check the major and
minor revisions set
for the target device
and connection. If
necessary, obtain
the most recent EDS
file and set it again.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.) Check that the
target device’s EDS file
is correct.
Check the originator’s
connection settings.
01
0117
Error code returned from target:
The tag set specified in the connec-
tion’s target variables does not exist.
Check whether the
originator and target
tag sets and tags are
set correctly.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufacturer.)
Check the originator’s
connection settings.
Check whether the tar-
get tag sets and tags
are set correctly.
Connection status
Source of error
Handling
General
Status
(hex)
Additional
Status
(hex)
Configuration 1
Configuration 2
Configuration 3