Appendices
A-16
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User’s Manual (W563)
After the tag set registration, set the connection settings for transferring data using the EtherNet/IP con-
nections.
Make the connection settings in the originator device (i.e., Controller 1 in this example) only.
Register the tag and tag set for Controller 2 (Target device) before setting the connection settings as
described in this example.
Refer to
Registering the Tag and Tag Set for the Target Device
on page A-24 for the operations for reg-
istering tags and tag sets.
Precautions for Correct Use
Precautions for Correct Use
If you change the IP address, model, or revision of the target device after making the connection
settings, you must also change the target device settings that are included in the connection set-
tings. For information on how to change the target device settings in the connection settings,
refer to
Changing the Target Device Settings After Making Connection Settings
.
1
Select
EtherNet/IP Connection Settings
from the Tools Menu to display the
EtherNet/IP
Device List Tab Page.
2
Right click
Built-in EtherNet/IP Port Settings
for Controller 1 (originator device in this example)
and select
Edit
from the menu.
The EtherNet/IP Connection Setting Tab Page is displayed.
3
Click the
(Show Connection Display) icon in the EtherNet/IP Connection Setting Tab Page.
4
Select
CJ1W-EIP21(NJ)
from
Target Device
in the Toolbox on the right of the tab page.
This operation displays the target device tag set
Net_Out1
that is set for Controller 2 in the
Variable Name
column.
Setting Connections for the Originator Device