![Omron Sysmac NY512-1300 User Manual Download Page 385](http://html.mh-extra.com/html/omron/sysmac-ny512-1300/sysmac-ny512-1300_user-manual_742451385.webp)
14-11
14 Checking Communications Status of Network and Troubleshooting
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User’s Manual (W563)
14-
2 Connection S
tatus Codes and T
roubleshootin
g
14
01
011A
Error code generated by originator:
Connection could not be established
because the buffer was full due to
high traffic.
Unexpected network
traffic may have
been received. Use
the Network Configu-
rator Device Monitor
or the Ethernet Tab
Page to check the
bandwidth usage,
and correct the load.
If there are places
where broadcast
storms occur, such
as loop connections
in the network con-
nection format, then
correct them.
Unexpected network
traffic may have been
received. Use the Net-
work Configurator
Device Monitor or the
Ethernet Tab Page to
check the bandwidth
usage, and correct the
load. If there are places
where broadcast
storms occur, such as
loop connections in the
network connection for-
mat, then correct them.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufacturer.)
01
011B
Error code returned from target:
The RPI was set to a value that is
below the specifications.
This error does not
occur.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufacturer.)
Set the originator’s RPI
setting to 1 ms or
greater.
01
0203
Error code generated by originator:
The connection timed out.
Tag data link communications from the target timed out. Check the power
supply and cable wiring of the devices in the communications path,
including the target and switches. If performance has dropped due to
heavy traffic, change the performance settings. For example, increase
the timeout time or RPI setting.
01
0204
Error code generated by originator:
The connection open process timed
out.
There was no response from the target. Check the power supply and
cable wiring of the devices in the communications path, including the tar-
get and switches.
01
0205
Error code returned from target:
There was a parameter error in the
frame used to open the connection.
This error does not
occur.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufacturer.)
Depends on the origi-
nator’s specifications.
(Contact the originator
device’s manufacturer.)
01
0302
Error code generated by originator
or returned from target:
The tag data link’s allowable band-
width (pps) was exceeded.
Check the connec-
tion settings (number
of connections and
RPI) at the origina-
tor and target.
Check the target’s con-
nection settings (num-
ber of connections and
RPI). Check the con-
nection settings (num-
ber of connections and
RPI) at the originator
and target.
Check the connection
settings (number of
connections and RPI)
at the originator and
target.
01
0311
Error code returned from target:
There was a parameter error in the
frame used to open the connection.
This error does not
occur.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufacturer.)
Depends on the origi-
nator’s specifications.
(Contact the originator
device’s manufacturer.)
01
0312
Error code returned from target:
There was a parameter error in the
frame used to open the connection.
This error does not
occur.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufacturer.)
Depends on the origi-
nator’s specifications.
(Contact the originator
device’s manufacturer.)
01
0315
Error code returned from target:
There was a parameter error in the
frame used to open the connection.
This error does not
occur.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufacturer.)
Depends on the origi-
nator’s specifications.
(Contact the originator
device’s manufacturer.)
01
0316
Error code returned from target:
There was a parameter error in the
frame used to close the connection.
This error does not
occur.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufacturer.)
Depends on the origi-
nator’s specifications.
(Contact the originator
device’s manufacturer.)
01
031C
Error code generated by originator:
Some other error occurred.
This error does not
occur.
The originator gener-
ates this code when an
unsupported response
code is returned from
the target in reply to an
open request.
Depends on the origi-
nator’s specifications.
(Contact the originator
device’s manufacturer.)
Connection status
Source of error
Handling
General
Status
(hex)
Additional
Status
(hex)
Configuration 1
Configuration 2
Configuration 3