7-3
7 Tag Data Link Functions
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User’s Manual (W563)
7-
1 Int
rod
uctio
n
t
o
T
ag D
at
a L
inks
7
7-1
-2 Dat
a Lin
k Da
ta Areas
A tag is a unit that is used to exchange data with tag data links. Data is exchanged between the local
network variables and remote network variables specified in the tags or between specified I/O memory
areas.
Precautions for Correct Use
Precautions for Correct Use
To maintain concurrency in the values of network variables that are assigned to tags, you must
set refreshing tasks. Refer to
7-1-7 Concurrency of Tag Data Link Data
for details.
When a connection is established, from 1 to 8 tags (including Controller status) is configured as a tag
set. Each tag set represents the data that is linked for a tag data link connection. Tag data links are
therefore created through a connection between one tag set and another tag set. A tag set name must
be set for each tag set.
Note
A connection is used to exchange data as a unit within which data concurrency is maintained. Thus, data
concurrency is maintained for all the data exchanged for the tags in one data set.
Precautions for Correct Use
Precautions for Correct Use
Data for the tags is exchanged in the order that the tags are registered in the tag sets. Register
the tags in the same order in the input and output tag sets.
7-1-2
Data Link Data Areas
Tags
Tag Sets