7 Tag Data Link Functions
7-56
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User’s Manual (W563)
You can upload tag data link parameters (such as the tag set settings and connection settings) from
EtherNet/IP Units in the EtherNet/IP network. The following procedure shows how to upload the param-
eters. For details on how to connect to the network from the Network Configurator, refer to
necting the Network Configurator to the Network
Precautions for Correct Use
Precautions for Correct Use
Make sure that the major CIP revision of the device registered with the Network Configurator is
the same as the major CIP revision of the Controller that you use. If the major CIP revisions are
not the same, the parameters may not be uploaded. To determine whether uploading is possi-
ble, refer to
There are two ways to upload the parameters.
Uploading from All Devices in the Network
1
Connect the Network Configurator online, and then select
Upload
from the Network Menu.
2
The following dialog box is displayed.
Clicking the Yes Button:
The tag data link parameters in the current project are uploaded.
Clicking the No Button:
You open a new project to upload the tag data link parameters. The current project is closed.
Clicking the Cancel Button:
The upload operation is cancelled. The upload is not performed.
3
If you click the
Yes
Button in step 2, the following dialog box is displayed.
Clicking the Yes Button:
Parameters are uploaded only from the devices registered in the Network Configuration Pane.
Parameters are not uploaded from devices that are not registered in the Network Configuration
Pane.
7-2-10 Uploading Tag Data Link Parameters
Summary of Contents for Sysmac NY512-1300