14 Checking Communications Status of Network and Troubleshooting
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User’s Manual (W563)
14-
1 Device
Mon
itorin
g
o
n
th
e Net
w
o
rk Con
fig
urato
r
14
14-
1-2 S
tatus Disp
lays
of the Device Monitor
ing
Tag Status Tab Page
This tab page displays if the tag settings for each tag for tag data links are set so that data can be
exchanged with the Controller. The following status is displayed depending on the status that is set.
If the status is not “Normal resolution completed,” check the tag data link settings or the network vari-
able settings in the variable table in the NY-series Controller.
•
Normal resolution completed:
Normal data exchange is possible.
•
Resolving:
The variables with tags are being resolved. When the
resolution is completed normally, a connection will be
established and the data exchange will start.
•
Size does not match error:
Different sizes are set for the network variables and the
tag settings. A connection will not be established for a
tag for which this error occurs.
•
No tag:
A network variable is not set in the variable table in the
Controller for the specified tag setting. A connection will
not be established for a tag for which this error occurs.
•
Attribute error:
1. Writing is not possible for Read Only and Constant
attributes.
2. The I/O direction that is set in the tag data link set-
tings does not agree with the I/O direction of the vari-
able in the Controller. There is an error in the setting
of a Network Publish attribute for a Controller vari-
able.
A connection will not be established for a tag for which
this error occurs.