![background image](http://html1.mh-extra.com/html/omron/sysmac-nx1p2-10-1-series/sysmac-nx1p2-10-1-series_user-manual_1633435166.webp)
5-5
SNMP Settings Display
SNMP
Setting
Description
Default
SNMP service
Specify whether to use the SNMP monitor service.
If the
Do not use
Option is selected, an SNMP manager cannot
connect from an external device.
Do not use
Port No.
Set the port number to use to connect to the SNMP server that is
used to connect from an SNMP manager.
This setting does not normally need to be changed.
161
Address
Set the communications device administrator’s name and instal-
lation location as text information. You do not necessarily have to
input all items. This information is read by the SNMP manager.
(You can input up to 255 single-byte alphanumeric characters for
each item.)
None
Location
None
Send a recognition
trap
Set whether to send an authentication trap.
If you select
Send a recognition trap
and there is access from
an SNMP manager that is not set in Recognition 1 or Recognition
2, an authentication trap is sent to the SNMP manager.
If you select
Send a recognition trap
, specify the SNMP trap
settings on the
SNMP Trap
Tab.
Not selected
*1.
If you select the Use Option for the SNMP service, you also have to set Recognition 1 and 2 as descri-
bed below.
*2.
The following ports are used by the system and cannot be set by the user: 25, 53, 68, 110, 2222, 2223,
2224, 9600, and 44818.
Additional Information
Refer to
on page 14-1 for details on the SNMP service.
5 Sysmac Studio Settings for the Built-in EtherNet/IP Port
5-12
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......