4
If the bandwidth usage rate is not set as desired even after the above operation, re-evaluate
the network configuration,considering the following points. (Refer to
• Reduce the number of nodes and connections
• Split the network
5
Check the bandwidth usage rate again.
After you change the connection settings, click the
Detail
Button in the
Usage of Device
Bandwidth
Area at the bottom of the Network Configuration Window to check the bandwidth
usage as described in
15-2-1 Checking Bandwidth Usage for Tag Data Links
It is important to check the bandwidth usage particularly after you change the RPI values for
individual connections, instead of setting the same RPI for all the connections.
6
Run user tests to verify that there are no problems with the new values.
15-2-5
RPI Setting Examples
The following examples explain how to calculate the packet intervals (RPIs) in the following network
configuration.
15 Communications Performance and Communications Load
15-16
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......