Variable name
Meaning
Function
Data type
Range of
values
Reference
_EIP2_TDLinkErr
CIP Communica-
tions2 Tag Data Link
Communications Er-
ror
Indicates that a timeout occurred in a tag
data link connection for CIP communica-
tions 2.
TRUE: A timeout occurred.
FALSE: Other than the above.
Note
You can use this system-de-
fined variable only for the
NX701 CPU Units and NX102
CPU Units.
BOOL
TRUE or
FALSE
_EIP_TagAdrErr
Tag Name Resolution
Error
NX-series CPU Units: Indicates that the
tag resolution for CIP communications 1
failed (i.e., the address could not be iden-
tified from the tag name).
TRUE: Tag resolution failed (i.e., the ad-
dress could not be identified from the tag
name). The following causes are possi-
ble.
•
The size of the network variable is dif-
ferent from the tag settings.
•
The I/O direction that is set in the tag
data link settings does not agree with
the I/O direction of the variable in the
CPU Unit.
•
There is no network variable in the
CPU Unit that corresponds to the tag
setting.
FALSE: Other than the above.
NJ-series CPU Units: Indicates that tag
name resolution failed (i.e., the address
could not be identified from the tag
name).
TRUE: Tag resolution failed (i.e., the ad-
dress could not be identified from the tag
name). The following causes are possi-
ble.
•
The size of the network variable is dif-
ferent from the tag settings.
•
The I/O direction that is set in the tag
data link settings does not agree with
the I/O direction of the variable in the
CPU Unit.
•
There is no network variable in the
CPU Unit that corresponds to the tag
setting.
FALSE: Other than the above.
BOOL
TRUE or
FALSE
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-16
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......