![Omron Sysmac NX1P2-10 1 Series User Manual Download Page 102](http://html1.mh-extra.com/html/omron/sysmac-nx1p2-10-1-series/sysmac-nx1p2-10-1-series_user-manual_1633435102.webp)
Variable name
Meaning
Function
Data type
Range of
values
Reference
_EIP1_TDLinkAll-
RunSta
CIP Communica-
tions1 All Tag Data
Link Communications
Status
Indicates that all tag data links are com-
municating in CIP communications 1.
TRUE: Tag data links are communicating
in all connections as the originator.
FALSE: An error occurred in at least one
connection.
Note
You can use this system-de-
fined variable only for NX-ser-
ies CPU Units.
BOOL
TRUE or
FALSE
_EIP2_TDLinkAll-
RunSta
CIP Communica-
tions2 All Tag Data
Link Communications
Status
Indicates that all tag data links are com-
municating in CIP communications 2.
TRUE: Tag data links are communicating
in all connections as the originator.
FALSE: An error occurred in at least one
connection.
Note
You can use this system-de-
fined variable only for the
NX701 CPU Units and NX102
CPU Units.
BOOL
TRUE or
FALSE
_EIP_RegTarget-
Sta[255]
Registered Target
Node Information
NX-series CPU Units: Gives a list of no-
des for which built-in EtherNet/IP connec-
tions are registered for CIP communica-
tions 1.
This variable is valid only when the built-
in EtherNet/IP port is the originator.
Array[x] is TRUE:
The connection to the node with a target
node ID of x is registered.
Array[x] is FALSE:
The connection to the node with a target
node ID of x is not registered.
NJ-series CPU Units: Gives a list of no-
des for which built-in EtherNet/IP connec-
tions are registered.
This variable is valid only when the built-
in EtherNet/IP port is the originator.
Array[x] is TRUE:
The connection to the node with a target
node ID of x is registered.
Array[x] is FALSE:
The connection to the node with a target
node ID of x is not registered.
ARRAY
[0..255] OF
BOOL
TRUE or
FALSE
_EIP1_RegTarget-
Sta[255]
CIP Communica-
tions1 Registered
Target Node Informa-
tion
Gives a list of nodes for which built-in
EtherNet/IP connections are registered
for CIP communications 1.
This variable is valid only when the built-
in EtherNet/IP port is the originator.
Array[x] is TRUE:
The connection to the node with a target
node ID of x is registered.
Array[x] is FALSE:
The connection to the node with a target
node ID of x is not registered.
Note
You can use this system-de-
fined variable only for NX-ser-
ies CPU Units.
ARRAY
[0..255] OF
BOOL
TRUE or
FALSE
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-24
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......