![background image](http://html1.mh-extra.com/html/omron/sysmac-nx1p2-10-1-series/sysmac-nx1p2-10-1-series_user-manual_1633435179.webp)
EtherNet/IP
Individual tags
I/O memory
CJ-series CPU Unit
Variable
c
Tag set
SP1_OUT
(tag
c
)
Connection
Connection
Tag set
SP1_IN
(tag
a
)
Tag set
SP2_IN
(tag
d
)
Tag set
SP2_OUT
(tag
b
)
Variable
d
Variable
b
Variable
a
NJ/NX-series CPU Unit
• Tag Sets Each with Multiple Tags
As shown below, multiple tags can be grouped. You can assign up to eight tags (up to 722 words
in total for an NX701 CPU Unit, and up to 300 words in total for an NX102, NX1P2, and NJ-ser-
ies CPU Unit) to one tag set.
EtherNet/IP
Individual tags
Connection
Tag set
SP2_IN
Connection
I/O memory
CJ-series CPU Unit
Tag set
SP1_OUT
Tag set
SP1_IN
(group of tags
a, b,
and
c
)
Tag set
SP2_OUT
(group of tags
d
and
e
)
Variable
j
Variable
i
Variable
h
Variable
g
Variable
f
Variable
e
Variable
d
Variable
c
Variable
b
Variable
a
NJ/NX-series CPU Unit
Note
To enable a connection, each tag set must include only one of ether input tags or output tags. (Both in-
put and output tags cannot be included in one tag set.)
7 Tag Data Link Functions
7-5
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
7-1 Introduction to T
ag Data Links
7
7-1-2
Data Link Data Areas
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......