Meanings of Error Status Bits
The meanings of the individual bits in the following error status are the same.
•
_ErrSta
(Controller Error Status)
•
_PLC_ErrSta
(PLC Function Module Error Status)
•
_CJB_ErrSta
(I/O Bus Error Status)
•
_CJB_MstrErrSta
(I/O Bus Master Error Status)
•
_CJB_UnitErrSta
(I/O Bus Unit Error Status)
•
_NXB_ErrSta
(NX Bus Function Module Error Status)
•
_NXB_MstrErrSta
(NX Bus Function Module Master Error Status)
•
_NXB_UnitErrStaTbl
(NX Bus Function Module Unit Error Status)
•
_MC_ErrSta
(MC Error Status)
•
_MC_ComErrSta
(MC Common Error Status)
•
_MC_AX_ErrSta
(Axis Error Status)
•
_MC_GRP_ErrSta
(Axes Group Error Status)
•
_EC_ErrSta
(Built-in EtherCAT Error)
•
_EC_PortErr
(Communications Port Error)
•
_EC_MstrErr
(Master Error)
•
_EC_SlavErr
(Slave Error)
•
_EC_SlavErrTbl
(Slave Error Table)
•
_EIP_ErrSta
(Built-in EtherNet/IP Error)
•
_EIP_PortErr
(Communications Port Error),
_EIP1_PortErr
(Communications Port1 Error),
_EIP2_PortErr
(Communications Port2 Error)
•
_EIP_CipErr
(CIP Communications Error),
_EIP1_CipErr
(CIP Communications1 Error),
_EIP2_CipErr
(CIP Communications2 Error)
•
_EIP_TcpAppErr
(TCP Application Communications Error)
The meanings of the bits are shown in the following table. However, do not use the following varia-
bles in the user program:
_ErrSta
(Controller Error Status),
_CJB_ErrSta
(I/O Bus Error Status),
_CJB_MstrErrSta
(I/O Bus Master Error Status),
_CJB_UnitErrSta
(I/O Bus Master Unit Status),
_NXB_ErrSta
(NX Bus Function Module Error Status),
_NXB_MstrErrSta
(NX Bus Function Module
Master Error Status), and
_NXB_UnitErrStaTbl
(NX Bus Function Module Unit Error Status). There
may be a delay in updating them and concurrency problems in relation to the error status of the
function module. Use these variables only to access status through communications from an exter-
nal device.
Bit:
1 5 1 4 1 3 1 2
-
11
-
-
-
1 0
-
9
-
8
7
6
5
4
-
3
-
1
-
2
WORD
-
0
Bit
Meaning
15
Master-detected error: This bit indicates whether the master detected a Controller error in the Unit/slave for
the error status of the Controller error.
TRUE: The master detected a Controller error.
FALSE: The master has not detected a Controller error. (Valid for
_CJB_UnitErrSta
.)
14
Collective slave error status: This bit indicates if a Controller error was detected for levels (e.g., a Unit, slave,
axis, or axes group) that are lower than the event source (i.e., for a function module).
TRUE: A Controller error has occurred at a lower level.
FALSE: A Controller error has not occurred at a lower level. (Valid for
_CJB_ErrSta
,
_MC_ErrSta
, and
_EC_ErrSta
.)
8 to 13
Reserved.
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-21
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
3-2 System-defined V
ariables
3
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......