A-1 Functional Comparison of EtherNet/IP
Ports on NJ/NX-series CPU Units and
Other Series
OK: Supported, ---: Not supported
Item
Built-in
EtherNet/
IP port
on NX701
CPU Unit
Built-in
EtherNet/
IP port
on NX102
CPU Unit
Built-in
EtherNet/
IP port
on
NX1P2
CPU Unit
Built-in
EtherNet/
IP port
on NJ-
series
CPU Unit
CJ-series
Ethernet
Unit
EtherNet/IP Unit (built-in port on
CJ2 CPU Unit)
Unit ver-
sion 1.0
Unit ver-
sion 2.0
Unit ver-
sion 2.1
Tag data link commu-
nications service
OK
OK
OK
OK
---
OK
OK
OK
CIP message commu-
nications service
OK
OK
OK
OK
---
OK
OK
OK
IP routing
OK
OK
---
---
---
---
---
---
Socket service
OK
OK
OK
OK
OK
---
---
---
FTP server
OK
OK
OK
OK
OK
---
OK
OK
FTP client
OK
OK
OK
OK
---
---
---
---
Mail send/receive
---
---
---
---
OK
---
---
---
Web functions
---
---
---
---
OK
---
---
---
Automatic adjustment
of PLC/Controller's in-
ternal clock
OK
OK
OK
OK
OK
---
OK
OK
Error history
OK
OK
OK
OK
OK
OK
OK
Response to PING
command
OK
OK
OK
OK
OK
OK
OK
OK
SNMP/SNMP trap
OK
OK
OK
OK
---
---
OK
OK
CIDR function for IP
addresses
OK
OK
OK
OK
---
---
OK
OK
Online connection via
EtherNet/IP using CX-
One
---
---
---
---
OK
---
OK
OK
Online connection via
EtherNet/IP using Net-
work Configurator
OK
OK
OK
OK
---
OK
OK
OK
Mounting in an NJ-
series CPU Unit
---
---
---
---
---
---
---
OK
Connection settings
using the Sysmac Stu-
dio
OK
OK
OK
OK
---
---
---
OK
*1.
This is equivalent to the event log in the built-in EtherNet/IP of an NJ-series Controller.
*2.
You cannot use the following functions if you connect to the CPU Unit through an EtherNet/IP Unit.
•
Placing the Sysmac Studio online with the CPU Unit (However, you can place the Network Configurator online)
•
Using the Troubleshooter of an NS-series PT
Appendices
A-2
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......