A-8-2
Changing the Unit Operation Settings for Multiple NX Units
Change the Unit operation settings for multiple NX Units mounted to the Controller. In this example,
the unit numbers of the NX Units are 1 and 2.
The following table gives the setting procedure.
Step
Description
CIP Object to use
Class ID
Instance ID
Service code
Unit
number
1
Change the parameter write
mode of the NX Unit with unit
number 1 to Write mode.
0x74
NX Configuration
object
0x01
0x37
Switch parameter
write mode
0x01
2
Change the parameter write
mode of the NX Unit with unit
number 2 to Write mode.
0x74
NX Configuration
object
0x01
0x37
Switch parameter
write mode
0x02
3
Write values to the NX object
of the NX Unit with unit num-
ber 1.
0x74
NX Configuration
object
0x01
0x34
Write NX object
0x01
4
Write values to the NX object
of the NX Unit with unit num-
ber 2.
0x74
NX Configuration
object
0x01
0x34
Write NX object
0x02
5
Save the values that are set in
the NX Unit with unit number
1.
0x74
NX Configuration
object
0x01
0x36
Save parameter
0x01
6
Save the values that are set in
the NX Unit with unit number
2.
0x74
NX Configuration
object
0x01
0x36
Save parameter
0x02
7
Restart the NX Unit with unit
number 1.
0x74
NX Configuration
object
0x01
0x35
Restart NX unit
0x01
8
Restart the NX Unit with unit
number 2.
0x74
NX Configuration
object
0x01
0x35
Restart NX unit
0x02
A-8-3
Initializing the Unit Operation Settings for Singe NX Unit
Initialize the Unit operation settings for a single NX Units mounted to the Controller. In this example,
the unit number of the NX Unit is 1.
The following table gives the setting procedure.
Step
Description
CIP Object to use
Class ID
Instance ID
Service code
Unit
number
1
Change the parameter write
mode of the NX Unit to Write
mode.
0x74
NX Configuration
object
0x01
0x37
Switch parameter
write mode
0x01
2
Initialize the Unit operation
settings for the NX Unit with
unit number 1.
0x74
NX Configuration
object
0x01
0x3D
Initialize unit opera-
tion parameter
0x01
3
Restart the NX Unit with unit
number 1.
0x74
NX Configuration
object
0x01
0x35
Restart NX unit
0x01
Appendices
A-63
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
A-8 Example of NX Unit Setting Using NX Configuration Object Service
A
A-8-2 Changing the Unit Operation Settings for Multiple NX Units
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......