Variable name
_EIP_TargetPLCModeSta[255]
Meaning
Target PLC Operating Mode
Global/local
Global
Function
NX-series CPU Units: Shows the operating status of the target node Controllers that are connected for CIP com-
munications 1, with the built-in EtherNet/IP port as the originator.
The array elements are valid only when the corresponding Normal Target Node Information is TRUE. If the corre-
sponding Normal Target Node Information is FALSE, it indicates the previous operating status.
Array[x] is TRUE: This is the operating state of the target Controller with a node address of x.
Array[x] is FALSE: Other than the above.
NJ-series CPU Units: Shows the operating status of the target node Controllers that are connected with the built-
in EtherNet/IP port as the originator.
The array elements are valid only when the corresponding Normal Target Node Information is TRUE. If the corre-
sponding Normal Target Node Information is FALSE, it indicates the previous operating status.
Array[x] is TRUE: This is the operating state of the target Controller with a node address of x.
Array[x] is FALSE: Other than the above.
Data type
ARRAY [0..255] OF BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
Variable name
_EIP1_TargetPLCModeSta[255]
Meaning
CIP Communications1 Target PLC Operating
Mode
Global/local
Global
Function
Shows the operating status of the target node Controllers that are connected for CIP communications 1, with the
built-in EtherNet/IP port as the originator.
The array elements are valid only when the corresponding Normal Target Node Information is TRUE. If the corre-
sponding Normal Target Node Information is FALSE, it indicates the previous operating status.
Array[x] is TRUE: This is the operating state of the target Controller with a node address of x.
Array[x] is FALSE: Other than the above.
Note
You can use this system-defined variable only for NX-series CPU Units.
Data type
ARRAY [0..255] OF BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
Variable name
_EIP2_TargetPLCModeSta[255]
Meaning
CIP Communications2 Target PLC Operating
Mode
Global/local
Global
Function
Shows the operating status of the target node Controllers that are connected for CIP communications 2, with the
built-in EtherNet/IP port as the originator.
The array elements are valid only when the corresponding Normal Target Node Information is TRUE. If the corre-
sponding Normal Target Node Information is FALSE, it indicates the previous operating status.
Array[x] is TRUE: This is the operating state of the target Controller with a node address of x.
Array[x] is FALSE: Other than the above.
Note
You can use this system-defined variable only for the NX701 CPU Units and NX102 CPU Units.
Data type
ARRAY [0..255] OF BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-56
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......