![Omron Sysmac NX1P2-10 1 Series User Manual Download Page 39](http://html1.mh-extra.com/html/omron/sysmac-nx1p2-10-1-series/sysmac-nx1p2-10-1-series_user-manual_1633435039.webp)
1-2
System Configuration and Configura-
tion Devices
1-2-1
Devices Required to Construct a Network
The basic configuration for an EtherNet/IP system includes one Ethernet switch to which nodes are
attached in star configuration using twisted-pair cable.
100 m
max.
Ethernet (LAN) port
(1) Built-in EtherNet/IP
port on NJ/NX-
series CPU Unit
(2) Twisted-pair cable
(3) Ethernet switch
Sysmac Studio
(Support Software)
(1) Built-in EtherNet/IP
port on NJ/NX-
series CPU Unit
(1) Built-in EtherNet/IP
port on NJ/NX-
series CPU Unit
The following products are also required to build a network. Obtain them in advance.
Network device
Function
Per Node
•
NJ-series CPU Unit (built-in EtherNet/IP port)
(NJ501-
££££
/NJ301-
££££
/NJ101-
££££
)
•
NX-series CPU Unit (built-in EtherNet/IP port)
(NX701-
££££
/NX102-
££££££
/NX1P2-
£££
£££
)
•
Other OMRON PLCs
CJ2 CPU Units (built-in EtherNet/IP port)
(CJ2H-CPU
££
-EIP/CJ2M-CPU3
£
)
CJ-series EtherNet/IP Unit
(CJ1W-EIP21)
CS-series EtherNet/IP Unit
(CS1W-EIP21)
These Units are used to connect to an EtherNet/IP
network.
(2)Twisted-pair cable
The twisted-pair cable has an RJ45 Modular Connec-
tor at each end.
This cable is used to connect the built-in EtherNet/IP
port or EtherNet/IP Unit to an Ethernet switch.
Use an STP (shielded twisted-pair) cable of category
5, 5e, or higher.
(3)Ethernet switch
This is a relay device that connects multiple nodes in a
star LAN.
For details on recommended devices to configure a
network, refer to
2-1-1 Recommended Network Devi-
*1.
The CJ1W-EIP21 EtherNet/IP Unit can be mounted only to an NJ-series CPU Unit. The unit version of the
NJ-series CPU Unit should be 1.01 or later, and the Sysmac Studio version should be 1.02 or higher.
1 Introduction
1-5
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
1-2 System Configuration and
Configuration Devices
1
1-2-1
Devices Required to Construct a Network
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......