13-2 Procedure to Use the Automatic
Clock Adjustment Function
13-2-1
Procedure
1
Make the basic settings.
Refer to
1-5 EtherNet/IP Communications Procedures
on page 1-28 for the basic operation
flow.
2
Select
Controller Setup
-
Built-in EtherNet/IP Port Settings
on the Sysmac Studio.
Set the following on the
NTP Settings
Display.
• NTP server settings (required)
• NTP operation timing
3
Select
Synchronization
from the
Controller
Menu. The built-in EtherNet/IP port settings are
transferred to the CPU Unit.
13-2-2
Settings Required for Automatic Clock Adjustment
The following Built-in EtherNet/IP Port Settings are made from the Sysmac Studio to use automatic
clock adjustment.
Tab page
Setting
Setting conditions
Reference
NTP
NTP server clock informa-
tion
Required.
Port No.
Specified by user.
Server specifying method
Required
IP address
One of these must be set, depending on
the
Server specification type
setting.
Host name
NTP operation timing
Required
Specify a Time
One of these must be set.
(Set according to the
NTP operation
timing
.)
Specify a time in-
terval
Timeout time
Specified by user.
*1.
Required to change from the default value of 123.
*2.
Required to change from the default value of 10 seconds.
Additional Information
Make the settings in the
NTP Settings
Display if automatic clock adjustment is used. Refer to
on page 5-10 for information on the
NTP Settings
Display.
13 Automatic Clock Adjustment
13-4
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......