Variable name
Meaning
Function
Data type
Range of
values
Reference
_EIP2_PortErr
Communications
Port2 Error
This is the error status variable for the
communications port 2.
It represents the collective status of the
following error flags.
•
_EIP2_MacAdrErr (Port2 MAC Ad-
dress Error)
•
_EIP2_LanHwErr (Port2 Communica-
tions Controller Error)
•
_EIP2_EtnCfgErr (Port2 Basic Ether-
net Setting Error)
•
_EIP2_IPAdrCfgErr (Port2 IP Address
Setting Error)
•
_EIP2_IPAdrDupErr (Port2 IP Address
Duplication Error)
•
_EIP2_BootpErr (Port2 BOOTP Serv-
er Error)
•
_EIP_DNSCfgErr (DNS Setting Error)
•
_EIP_DNSSrvErr (DNS Server Con-
nection Error)
•
_EIP_IPRTblErr (IP Route Table Error)
Note
If a Link OFF Detected or Built-
in EtherNet/IP Processing Er-
ror occurs, it is recorded in the
event log and then the corre-
sponding bit turns ON.
Refer to information on the
meanings of the error status
bits at the end of this appendix
for details.
Note
You can use this system-de-
fined variable only for the
NX701 CPU Units and NX102
CPU Units.
WORD
16#0000 to
16#00F0
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-6
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......