Precautions for Correct Use
Communications Status with Target Node
The communications status with the target node of an NJ/NX-series Controller is shown by the
combination of the values of four system-defined variables.
• _EIP_RegTargetSta (Registered Target Node Information)
• _EIP_EstbTargetSta (Normal Target Node Information)
• _EIP_TargetPLCErr (Target PLC Error Information)
• _EIP_TargetNodeErr (Target Node Error Information)
Value of
_EIP_RegTarget-
Sta
Value of
_EIP_EstbTar-
getSta
Value of
_EIP_Tar-
getPLCErr
Value of
_EIP_Target-
NodeErr
Communications status
with target node
TRUE
TRUE
FALSE
FALSE
A connection with the target
node was established normal-
ly and there is no error in the
target PLC.
TRUE
TRUE
A connection with the target
node was established but
there is an error in the target
PLC.
FALSE
---
TRUE
A connection with the target
node was not established nor-
mally.
FALSE
---
---
---
The information is not valid
because the target node is not
registered.
For the NX-series Controller, the communications status of CIP communications 1 and CIP
communications 2 is shown by the combination of the values of four system-defined variables in
the same way as shown in the above table.
• CIP Communications 1
• _EIP1_RegTargetSta (CIP Communications1 Registered Target Node Information)
• _EIP1_EstbTargetSta (CIP Communications1 Normal Target Node Information)
• _EIP1_TargetPLCErr (CIP Communications1 Target PLC Error Information)
• _EIP1_TargetNodeErr (CIP Communications1 Target Node Error Information)
• CIP Communications 2
• _EIP2_RegTargetSta (CIP Communications2 Registered Target Node Information)
• _EIP2_EstbTargetSta (CIP Communications2 Normal Target Node Information)
• _EIP2_TargetPLCErr (CIP Communications2 Target PLC Error Information)
• _EIP2_TargetNodeErr (CIP Communications2 Target Node Error Information)
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-33
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
3-2 System-defined V
ariables
3
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......