Additional Information
• Change the Tag Data Link Communications Start Switch to TRUE, while the Tag Data Link
Communications Stop Switch is FALSE.
If the Tag Data Link Communications Stop Switch is TRUE, the tag data links do not start
even if the Tag Data Link Communications Start Switch is changed to TRUE.
Furthermore, if the Tag Data Link Start Switch and the Tag Data Link Stop Switch are both
TRUE, an error occurs, the Multiple Switches ON Error system-defined variable changes to
TRUE, and the event is recorded in the event log.
• After you start the tag data links, do not force the Tag Data Link Communications Start Switch
to change to FALSE from the user program or from the Sysmac Studio. It will change to
FALSE automatically.
Using the Network Configurator
You can select
I/O Connection
-
Start
or
Stop
from the
Network
Menu to start and stop tag data
links for individual devices.
Starting and Stopping Tag Data Links for Individual Devices
Using the Network Configurator
You can start and stop tag data links on a device basis (at the originator) by selecting
Monitor
from
the
Device
Menu and performing the following operation in the
Connection
Tab Page in the
Monitor Device
Dialog Box.
When using an NX701 CPU Unit or NX102 CPU Unit, you can start and stop tag data links for each
of the built-in EtherNet/IP port 1 and 2 connected to the Network Configurator.
Start Connection
Button:
Starts all connections for which the device is the originator.
Stop Connection
Button:
Stops all connections for which the device is the originator.
7 Tag Data Link Functions
7-70
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......