Parameter name
Data type
Description
Unit No
UINT
Unit number
0000 hex: Controller
0001 to 0020 hex: NX Unit
0021 hex or above: Not supported
Event log type
UINT
Event log type
0000 hex: System event log
0001 hex: Access event log
0002 hex: User event log
Start index of read record
UDINT
Top index number of read record
If the record specified by the Start index of read re-
cord is not found in the Unit, the record will be read
from the oldest index. If the maximum number of
event log records which can be registered for the
Unit is exceeded, this will occur since old records
are overwritten by new records.
Number of read record
UINT
Number of read records
Controller (0 to 5)
NX Units (0 to 9)
When the registered number of records is smaller
than the number of read records, an error does not
occur, and all the registered event logs are read.
Response Data Format
When the processing is successful
Parameter name
Data type
Description
Reply Service
USINT
Get event log service response: BB hex
Reserved
USINT
Reserved: 00 hex
General Status
USINT
Code indicating normal: 00 hex
Size of Additional Status
USINT
Size of Additional Status: 00 hex
Record size
UINT
Size of one record (Byte)
Controller event log: 0060 hex
NX Unit event log: 0032 hex
Number of registered record
UINT
Number of registered records
Latest index of registered record UDINT
Index number of the latest registered record
Last index of readout record
UDINT
Index number of last readout record
Number of readout record
UINT
Number of readout records
Reserved
UINT
Reserved
8 CIP Message Communications
8-63
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
8-5
CIP Object Services
8
8-5-3
NX Configuration Object (Class ID: 74 hex)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......