![Omron Sysmac NX1P2-10 1 Series User Manual Download Page 120](http://html1.mh-extra.com/html/omron/sysmac-nx1p2-10-1-series/sysmac-nx1p2-10-1-series_user-manual_1633435120.webp)
Variable name
_EIP2_EtnCfgErr
Meaning
Port2 Basic Ethernet Setting Error
Global/local
Global
Function
Indicates that the Ethernet communications speed setting (Speed/Duplex) for the communications port 2 is incor-
rect. Or, a read operation failed.
TRUE: Setting incorrect or read failed.
FALSE: Normal
Note
You can use this system-defined variable only for the NX701 CPU Units and NX102 CPU Units.
Data type
BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
Variable name
_EIP_IPAdrCfgErr
Meaning
IP Address Setting Error
Global/local
Global
Function
NX-series CPU Units: Indicates the IP address setting errors for the communications port 1.
TRUE:
•
There is an illegal IP address setting.
•
A read operation failed.
•
The IP address obtained from the BOOTP server is inconsistent.
FALSE: Normal
NJ-series CPU Units: Indicates the IP address setting errors.
TRUE:
•
There is an illegal IP address setting.
•
A read operation failed.
•
The IP address obtained from the BOOTP server is inconsistent.
•
The default gateway settings are not correct.
FALSE: Normal
Data type
BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
Variable name
_EIP1_IPAdrCfgErr
Meaning
Port1 IP Address Setting Error
Global/local
Global
Function
Indicates the IP address setting errors for the communications port 1.
TRUE:
•
There is an illegal IP address setting.
•
A read operation failed.
•
The IP address obtained from the BOOTP server is inconsistent.
FALSE: Normal
Note
You can use this system-defined variable only for NX-series CPU Units.
Data type
BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Related in-
structions
Related in-
structions
---
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-42
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......