You can register up to 8 tags in a tag set.
Set as shown below to register multiple tags.
Examples:
Tag set name
▼
Network_Input_Value
.... (Tag set name)
Net_In1
.... (Tag name)
Net_In2
.... (Tag name)
6
Register all tags and tag sets at the same time.
1) Right-click anywhere on the Input Tab Page of the EtherNet/IP Connection Settings Tab
Page and select
Register All Tag Sets
or click the
Registration All
Button to display the
Tag Set Registration Setting
Dialog Box.
This dialog box lists the variables that are registered in the Global Variable Table and
also have the
Network Publish
attribute set to
Input
or
Output
.
2) Select the variable to register as a tag, and then click the
Register
Button.
3) The automatically registered tag is added to the list in the EtherNet/IP Connection Setting
Tab Page.
With automatic registration, the tag is registered under a tag set having the same name
as the tag, i.e., a single tag is registered in a single tag set.
Tag set name
Tag name
7
Set the following settings for the registered tag and tag set.
Appendices
A-13
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
A-2 Use the Sysmac Studio to Set the T
ag Data Links (EtherNet/IP Connections)
A
A-2-4 Making the EtherNet/IP Connection Settings with the Sysmac Stu-
dio
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......