The name and size of the tag must be the same as those of the network variable
*1
. Set whether to
include the Controller status information in tags for the tag sets. You can also set the data output
operation at a fatal error occurrence for output tags.
Refer to
Registering the Tag and Tag Set
on page A-11 for information on how to register tags and
tag sets.
*1. A variable with its
Network Publish attribute
set to
Output
or
Input
in the Global Variable Table is called a
network variable.
EtherNet/IP Connection Settings (Connection Display)
Specify the target devices and set their connections.
For each connection, set the following information: Connection Name, Connection I/O Type, I/O, target
device tag set (target variable), originator device tag set (originator variable), Packet Interval (RPI),
and Timeout Value.
Refer to
Setting Connections for the Originator Device
on page A-14 for information on how to make
connection settings.
Precautions for Correct Use
If you changed the IP address, model or revision of the target device after making the connec-
tion settings, perform the following.
With the Sysmac Studio version 1.11 or higher, change the connection settings entirely.
With the Sysmac Studio version 1.10 or lower, create the connections again.
Appendices
A-7
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
A-2 Use the Sysmac Studio to Set the T
ag Data Links (EtherNet/IP Connections)
A
A-2-3 EtherNet/IP Connection Settings
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......