![Omron Sysmac NX1P2-10 1 Series User Manual Download Page 158](http://html1.mh-extra.com/html/omron/sysmac-nx1p2-10-1-series/sysmac-nx1p2-10-1-series_user-manual_1633435158.webp)
Operation at IP Address Duplication
Setting
Description
Default
Use of duplicated IP ad-
dress
When you set an IP address for the built-in EtherNet/IP port and
find an IP address conflict with another node, select whether to
stop the use of the IP address.
•
Stop
If the IP address conflict is not resolved for a certain length of
time, the use of the IP address is stopped, and an IP Address
Duplication Error will occur.
•
Do not stop
You continue to use the IP address and wait until the duplicate
IP address of the other node is changed.
Stop
*1.
For systems that use OPC UA to connect to an information system network, it is recommended that you
set this to
Do not stop
.
Version Information
The setting for the
Use of duplicated IP address
can be used with the CPU Units that support
OPC UA, and the Sysmac Studio. Refer to the
NJ/NX-series CPU Unit OPC UA User’s Manual
(Cat. No. W588)
for information on the models and unit versions of the CPU Units that support
OPC UA, and the Sysmac Studio version.
DNS
Setting
Description
Default
Use/
Do not use DNS
When you specify a host name for CIP communications instruc-
tions, socket instructions or NTP server settings, select the
Use
Option if you use DNS for resolving host name.
A DNS server is required to use DNS.
Do Not Use
Priority DNS server
Set the IP address of the DNS server.
You can set priority and secondary IP addresses.
None
Secondary DNS server
None
Set the domain name of the domain to which the built-in Ether-
Net/IP port belongs.
(Single-byte alphanumeric characters, dots, and hyphens: 48
characters max.)
None
*1.
These settings are required if you select the
Use
Option for
DNS
.
Host Name - IP Address
Setting
Description
Default
Host name
Addresses are converted according to this setting when a host
name is used to specify remote communications nodes.
Host names can be set whether DNS is used or not.
You can set up to six host names.
(You can use up to 200 single-byte alphanumeric characters,
dots, and hyphens, including up to 63 single-byte alphanumeric
characters between dots.)
None
IP address
Set the IP address of the registered host name.
None
5 Sysmac Studio Settings for the Built-in EtherNet/IP Port
5-4
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......