Variable name
Meaning
Function
Data type
Range of
values
Reference
_EIP1_IPAdrDupErr
Port1 IP Address Du-
plication Error
Indicates that the same IP address is as-
signed to more than one node for the
communications port 1.
TRUE: Duplication occurred.
FALSE: Other than the above.
Note
You can use this system-de-
fined variable only for NX-ser-
ies CPU Units.
BOOL
TRUE or
FALSE
_EIP2_IPAdrDupErr
Port2 IP Address Du-
plication Error
Indicates that the same IP address is as-
signed to more than one node for the
communications port 2.
TRUE: Duplication occurred.
FALSE: Other than the above.
Note
You can use this system-de-
fined variable only for the
NX701 CPU Units and NX102
CPU Units.
BOOL
TRUE or
FALSE
_EIP_DNSCfgErr
DNS Setting Error
Indicates that the DNS or hosts settings
are incorrect. Or, a read operation failed.
TRUE: Setting incorrect or read failed.
FALSE: Normal
BOOL
TRUE or
FALSE
_EIP_BootpErr
BOOTP Server Error
NX-series CPU Units: Indicates that a
BOOTP server connection failure occur-
red on the communications port 1.
TRUE: There was a failure to connect to
the BOOTP server (timeout).
FALSE: The BOOTP is not enabled, or
BOOTP is enabled and an IP address
was normally obtained from the BOOTP
server.
NJ-series CPU Units: Indicates that a
BOOTP server connection failure occur-
red.
TRUE: There was a failure to connect to
the BOOTP server (timeout).
FALSE: The BOOTP is not enabled, or
BOOTP is enabled and an IP address
was normally obtained from the BOOTP
server.
BOOL
TRUE or
FALSE
_EIP1_BootpErr
Port1 BOOTP Server
Error
Indicates that a BOOTP server connec-
tion failure occurred on the communica-
tions port 1.
TRUE: There was a failure to connect to
the BOOTP server (timeout).
FALSE: The BOOTP is not enabled, or
BOOTP is enabled and an IP address
was normally obtained from the BOOTP
server.
Note
You can use this system-de-
fined variable only for NX-ser-
ies CPU Units.
BOOL
TRUE or
FALSE
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-12
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......