10
To register the newly added tags in an existing tag set, either double-click the desired tag set,
or select the tag set and click the
Edit
Button.
The Tag List on the left side of the dialog box shows tags that are already registered in the tag
set, and the Candidate Tag List on the right side of the dialog box shows the other tags that are
not registered yet.
11
Select the tags that you want to add from the Candidate Tag List and click the
Button.
You can register up to eight tags in a tag set. (If you include the Controller status in the tag set,
you can register up to only seven tags, and two bytes are added to the size.)
Tag data is sent and received in the order of tags displayed in the tag list. To change the order
of tag data, select a tag and click the
or
Button.
12
To confirm the change, click the
OK
Button in the
Edit Tag Set
Dialog Box.
7 Tag Data Link Functions
7-32
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......