Precautions for Correct Use
Adjust the built-in EtherNet/IP port's link settings to match the communications mode settings of
the connected Ethernet switch. If the settings do not match, the link will be unstable and prevent
normal communications. The following table shows the allowed settings for each Ethernet
switch communications mode.
(Auto-Nego: Auto negotiation, Full: Full duplex, Half: Half duplex)
Ethernet switch
Built-in EtherNet/IP port
Auto-
Nego
10 Mbps (fixed)
100 Mbps (fixed)
1,000 Mbps
(fixed)
Full
Half
Full
Half
Full
Auto-Nego
Best
---
OK
---
OK
---
10 Mbps
(fixed)
Full
---
OK
---
---
---
---
Half
OK
---
OK
---
---
---
100 Mbps
(fixed)
Full
---
---
---
OK
---
---
Half
OK
---
---
---
OK
---
1,000 Mbps
(fixed)
Full
---
---
---
---
---
Best
Best = Recommended; OK = Allowed; --- = Not allowed.
2 Installing Ethernet Networks
2-12
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......