![Omron Sysmac NX1P2-10 1 Series User Manual Download Page 275](http://html1.mh-extra.com/html/omron/sysmac-nx1p2-10-1-series/sysmac-nx1p2-10-1-series_user-manual_1633435275.webp)
(b)
(c)
(d)
(a)
Backplane
port (#01)
Backplane
port (#01)
NX701 CPU Unit or NX102 CPU Unit
NX701 CPU Unit or NX102 CPU Unit (Relay unit)
NX701 CPU Unit or NX102 CPU Unit
CPU#00
(Unit address
00 hex)
CPU#01
(Unit address
01 hex)
CPU#00
(Unit address
00 hex)
CPU#01
(Unit address
01 hex)
CPU#00
(Unit address
00 hex)
CPU#01
(Unit address
01 hex)
Built-in EtherNet/IP
port 1
Built-in EtherNet/IP
port 2
Built-in EtherNet/IP
port 1
Built-in EtherNet/IP
port 2
Built-in EtherNet/IP
port 1
Built-in EtherNet/IP
port 2
Communications
port (#02)
Communications
port (#02)
Communications
port (#02)
Communications
port (#02)
Communications
port (#02)
Communications
port (#02)
IP address :
192.168.251.2
IP address :
192.168.252.3
a) Local backplane to local CPU #01
• Network type number: "01" (Output to Backplane port)
• Destination address: "#01" (CPU#01) Note: This is in order to output using the sender IP
address of the built-in EtherNet/IP port 2.
b) Local CPU #01 to destination IP address
• Network type number: "02" (Output to the communications port)
• Destination address: Specify the destination IP address
c) Relay backplane to relay CPU #00
• Network type number: "01" (Output to Backplane port)
• Destination address: "#00" (CPU#00) Note: This is in order to output using the sender IP
address of the built-in EtherNet/IP port 1.
d) Relay CPU #00 to destination IP address
• Network type number: "02" (Output to the communications port)
• Destination address: Specify the destination IP address
Route Path : 01\#01\02\192.168.251.2\01\#00\02\192.168.252.3
(a)
(b)
(c)
(d)
NX1P2 CPU Unit
This section provides examples of route paths.
1. Communicating between Built-in EtherNet/IP Ports
Example: Communicating between the built-in EtherNet/IP ports on CPU Unit 1 and CPU
Unit 2
CPU Unit #1
Built-in EtherNet/IP port
Built-in EtherNet/IP port
IP address
192.168.250.2
CPU Unit #2
Communications port (#02)
CPU#00
(Unit address 00 hex)
Communications port (#02)
• Network type number: "#02" (Output the command via the built-in EtherNet/IP port)
• Destination address: Specify the destination IP address
8 CIP Message Communications
8-13
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
8-2 CIP Message Communications Client Function
8
8-2-4
Route Path
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......