![Omron Sysmac NX1P2-10 1 Series User Manual Download Page 164](http://html1.mh-extra.com/html/omron/sysmac-nx1p2-10-1-series/sysmac-nx1p2-10-1-series_user-manual_1633435164.webp)
5-4
NTP Settings Display
Setting
Description
Default
NTP server clock infor-
mation
Set whether to obtain clock information from the NTP server to up-
date the clock in the CPU Unit.
Do not get
Set the port number to use to connect to the NTP server to obtain
clock information. It is normally not necessary to change this set-
ting.
123
Server specifying meth-
od
Set the method to use to specify the NTP server to obtain clock in-
formation.
•
IP address
•
Host name
IP address
IP address
Set the IP address of the NTP server.
Specify this setting if the
server specifying method
is set to the
IP
address
Option.
None
Host name
Set the host name of the NTP server (i.e., the domain name of the
host).
Specify this setting if the
server specifying method
is set to the
Host name
Option.
(You can use up to 200 single-byte alphanumeric characters, dots,
and hyphens, including up to 63 single-byte alphanumeric charac-
ters between dots.)
None
NTP operation timing
Set the time at which the NTP server is accessed to synchronize
the clocks.
•
Specify a time
•
Specify a time interval
Specify a time
Time [hours:mi-
nutes:seconds]
The NTP server is accessed at the specified time.
(Setting range: 00:00:00 to 23:59:59)
Specify this setting if the
NTP operation timing
is set to the
Specify a time
Option.
00:00:00
Interval [minutes]
The NTP server is accessed when the specified period of time has
passed.
(Setting range: 1 to 1,440 minutes)
Specify this setting if the
NTP operation timing
is set to the
Specify a time interval
Option.
60 minutes
5 Sysmac Studio Settings for the Built-in EtherNet/IP Port
5-10
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......