![Omron Sysmac NX1P2-10 1 Series User Manual Download Page 527](http://html1.mh-extra.com/html/omron/sysmac-nx1p2-10-1-series/sysmac-nx1p2-10-1-series_user-manual_1633435527.webp)
3
Click the
(Show Tag Set Display) icon in the EtherNet/IP Connection Setting Tab Page.
4
Click the
Output
tab to switch to the
Output
Tab Page. Register the following tag and tag set.
The tag and tag set can be registered in the same way as for the target device. (Refer to
Checking the Device Bandwidth Usage
The bandwidth usage for the device can be displayed from the EtherNet/IP Connection Setting Tab
Page.
This value is for when multicast filtering is used.
Precautions for Correct Use
In the Device Bandwidth Dialog Box, you can only check the bandwidth being used for the
EtherNet/IP connections from one originator device to its target devices.
The actual bandwidth used for the EtherNet/IP network must be calculated by taking into ac-
count of all bandwidths used on the EtherNet/IP network (i.e., bandwidths used for connections
for the other devices in the EtherNet/IP network than the one given on the dialog box must be
included into the calculation).
Procedure
Click the
Device Bandwidth
Button in the EtherNet/IP Connection Setting Tab Page for the target
device.
Appendices
A-23
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
A-2 Use the Sysmac Studio to Set the T
ag Data Links (EtherNet/IP Connections)
A
A-2-4 Making the EtherNet/IP Connection Settings with the Sysmac Stu-
dio
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...