![Omron Sysmac NX1P2-10 1 Series User Manual Download Page 126](http://html1.mh-extra.com/html/omron/sysmac-nx1p2-10-1-series/sysmac-nx1p2-10-1-series_user-manual_1633435126.webp)
Variable name
_EIP_TDLinkErr
Meaning
Tag Data Link Communications Error
Global/local
Global
Function
NX-series CPU Units: Indicates that a timeout occurred in a tag data link connection for CIP communications 1.
TRUE: A timeout occurred.
FALSE: Other than the above.
NJ-series CPU Units: Indicates that a timeout occurred in a tag data link connection.
TRUE: A timeout occurred.
FALSE: Other than the above.
Data type
BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
Variable name
_EIP1_TDLinkErr
Meaning
CIP Communications1 Tag Data Link Communi-
cations Error
Global/local
Global
Function
Indicates that a timeout occurred in a tag data link connection for CIP communications 1.
TRUE: A timeout occurred.
FALSE: Other than the above.
Note
You can use this system-defined variable only for NX-series CPU Units.
Data type
BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
Variable name
_EIP2_TDLinkErr
Meaning
CIP Communications2 Tag Data Link Communi-
cations Error
Global/local
Global
Function
Indicates that a timeout occurred in a tag data link connection for CIP communications 2.
TRUE: A timeout occurred.
FALSE: Other than the above.
Note
You can use this system-defined variable only for the NX701 CPU Units and NX102 CPU Units.
Data type
BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-48
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......