STP
(Shield)
STP
(Shield)
GR
terminal
GR
terminal
Ethernet switches
GR
terminal
Connector
Connector
Connector
Connector
Connector
Built-in EtherNet/IP
port
Clamp core
Built-in EtherNet/IP
port on NX-series
CPU Unit
Power Supply
Unit
Built-in EtherNet/IP
port on NJ-series
CPU Unit
Power Supply
Unit
Connect shield to connector hood
Do not connect shield to connector hood
Additional Information
Noise immunity may be reduced and device damage may occur due to ground loops, which
may be caused by improper shield connections and grounding methods.
When using a baud rate of 100 Mbps or less, it may be possible to alleviate this problem by
connecting the shield only at the Ethernet switch side as described in (2), rather than connect-
ing both ends as described in (1).
• 1000Base-T
Connect the shields to respective connector hoods at both ends of the cables.
This connection is required for 1000Base-T to ensure compliance with EMC standards.
STP
(Shield)
STP
(Shield)
Built-in EtherNet/IP
port on NX-series
CPU Unit
GR
terminal
Power Supply
Unit
Built-in EtherNet/IP
port on NX-series
CPU Unit
Power Supply
Unit
GR
terminal
Ethernet switches
GR
terminal
Connector
Connector
Connector
Connector
Connector
Connect shield to connector hood
Built-in
EtherNet/IP port
2 Installing Ethernet Networks
2-9
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
2-2
Network Installation
2
2-2-3
Precautions When Laying T
wisted-pair Cable
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......