Controller user event log
Parameter name
Data type
Description
Index
UDINT
Event log index number
This number is assigned when system event logs
and access event logs are registered.
Event occurred time
ULINT
Event occurred time
Event source
UINT
Event source
Event priority
UINT
Event level
Event code
UDINT
Event code
Event priority details
UINT
Event level details
Additional information[0]
to
Additional information[39]
Array of BYTE
Attached information (system information) of event.
Reserved[0]
to
Reserved[31]
Array of BYTE
Reserved
NX Unit
Parameter name
Data type
Description
Index
UDINT
Event log index number
This number is assigned when system event logs
and access event logs are registered.
Unit number
USINT
Unit number
0000 hex: Controller
0001 to 0020 hex: NX Unit
Event priority
USINT
Event level
Event occurred time
UDINT
Event occurred time
Product code
UDINT
Product code of the Unit in which event occurred
Event code
UDINT
Event code
Additional information[0]
to
Additional information[31]
Array of BYTE
Attached information (system information) of event.
CIP Error Codes
General sta-
tus code
(hex)
Error name
Cause
02
Resource unavailable
Resources needed for the object to perform the requested
service were unavailable.
0C
Object state conflict
The object cannot perform the requested service in its cur-
rent mode/state.
13
Not enough data
Data required for the execution of the required service is in-
sufficient.
15
Too much data
Extra data for the execution of the required service is includ-
ed.
1F
Vendor specific error
The service could not be executed due to internal reasons.
8 CIP Message Communications
8-65
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
8-5
CIP Object Services
8
8-5-3
NX Configuration Object (Class ID: 74 hex)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......