![background image](http://html1.mh-extra.com/html/omron/sysmac-nx1p2-10-1-series/sysmac-nx1p2-10-1-series_user-manual_1633435536.webp)
Name
Description
Tag Name
The current status of each tag is indicated by its color.
Red: Tag name resolution error
Blue: Tag name resolution normal
Gray: Not yet transferred (no information in device).
Input/Output
Gives the type of the tag.
Status
The following status is displayed depending on the status that is set.
•
Normally resolved: Normal data exchange is possible.
•
Different sizes: Different sizes are set for the network variables and the tag
settings.
A connection will not be established for a tag for which this error occurs.
•
No tag: A network variable is not set in the variable table in the CPU Unit
for the specified tag setting.
A connection will not be established for a tag for which this error occurs.
•
Attribute error: The following two factors cause this error.
1. Writing is not possible for constant attributes.
2. The I/O direction that is set in the tag data link settings does not agree
with the I/O direction of the variable in the CPU Unit. There is an error in
the setting of a Network Publish attribute for a CPU Unit variable.
A connection will not be established for a tag for which this error occurs.
•
Output Tag Set
and
Input Tag Set
Tab Pages
You can monitor the status of each input/output tag set that is used for the EtherNet/IP connections.
Note
The tag set status monitor is not available for a built-in EtherNet/IP port on NJ-series Controller version
1.08 or earlier.
Click ▼ of each tag to display its detailed information.
Name
Description
Tag Set Name
Gives the connection status.
If there is a connection error, "Not connected or error" is given.
Tag set size
Gives the size of the tag set in bytes.
Appendices
A-32
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......