Output data is cleared to 0 when a major fault occurs.
Select the
Hold
or
Clear
Option.
Precautions for Correct Use
Connections are cut off if any of the following errors occurs in the CPU Unit that is the originator
while tag data links are active.
• Major fault level Controller error
• Partial fault level Controller error
7
After you register all of the required tags, click the
OK
Button in the
Edit Tags
Dialog Box.
Precautions for Correct Use
Make the following settings to refresh all of the tag data in one tag set at the same time.
• Use the Sysmac Studio, in advance, to specify the same refreshing task for all of the varia-
bles that are assigned to tags in the tag set.
• Do not place tag variables that have AT specifications in I/O memory and tag variables that
do not have AT specifications in the same tag set.
8
At this point, a confirmation dialog box is displayed to check whether the registered tag names
are used as the tag set names. A tag set can contain up to eight tags, but tag sets are
7 Tag Data Link Functions
7-28
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......