Attribute ID
Parameter name
Description
Attrib-
ute
Read/write data
Data
type
Value
02 hex
Configuration Capabil-
ity
Indicates a Controller Con-
figurations and Setup that
can be set to the interface.
Read
DWOR
D
Bit 0: BOOTP Client: Always
TRUE.
Bit 1: DNS Client: Always
TRUE.
Bit 2: DHCP Client: Always
FALSE.
Bit 3: DHCP-DNS Update: Al-
ways FALSE.
Bit 4: Configuration Settable:
Always TRUE.
Bit 5: Hardware Configurable:
Always FALSE.
Bit 6: Interface Configuration
Change Requires Reset: Al-
ways FALSE.
bit7: ACD Capable
: Always
TRUE.
Bits 8 to 31: Reserved (always
FALSE).
03 hex
Configuration Control
Sets the method used to set
the IP address when the in-
terface starts.
Read/
Write
DWOR
D
Bit 0 to 3: IP Address Setting
Method
0 = Setting the static IP ad-
dress.
1 = Setting by BOOTP.
Bit 4: DNS Enable/Disable
Setting
FALSE = DNS disabled.
TRUE = DNS enabled.
Bits 5 to 31: Reserved (always
FALSE).
04 hex
Physical Link Object
The path to the link object in
the physical layer.
Read
Struct
---
Path size
The path size (WORD size).
UINT
0002 hex
Path
The path to the link object in
the physical layer (static).
EPATH
20 F6 24 01 hex
05 hex
Interface Configura-
tion
The interface settings.
Read/
Write
Struct
---
IP Address
IP address.
UDINT
Set value
Network Mask
Subnet mask.
UDINT
Set value
Gateway Address
The default gateway.
UDINT
Set value
Name Server
The primary name server.
UDINT
Set value
Name Server2
The secondary name server.
UDINT
Set value
Domain Name
The domain name.
STRIN
G
06 hex
Host Name
The host name (reserved).
Read/
Write
STRIN
G
*1.
The value is always FALSE for a CPU Unit with unit version 1.01 or earlier.
*2.
The value is the size of domain name (2 bytes) + domain name (48 bytes max.).
*3.
The value is the size of host name (2 bytes) + host name (64 bytes max.).
8 CIP Message Communications
8-74
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......