![background image](http://html1.mh-extra.com/html/omron/sysmac-nx1p2-10-1-series/sysmac-nx1p2-10-1-series_user-manual_1633435128.webp)
Variable name
_EIP2_TagAdrErr
Meaning
CIP Communications2 Tag Name Resolution
Error
Global/local
Global
Function
Indicates that the tag resolution for CIP communications 2 failed (i.e., the address could not be identified from the
tag name).
TRUE: Tag resolution failed (i.e., the address could not be identified from the tag name). The following causes are
possible.
•
The size of the network variable is different from the tag settings.
•
The I/O direction that is set in the tag data link settings does not agree with the I/O direction of the variable in
the CPU Unit.
•
There is no network variable in the CPU Unit that corresponds to the tag setting.
FALSE: Other than the above.
Note
You can use this system-defined variable only for the NX701 CPU Units and NX102 CPU Units.
Data type
BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
Variable name
_EIP_MultiSwONErr
Meaning
Multiple Switches ON Error
Global/local
Global
Function
NX-series CPU Units: Indicates that more than one switch turned ON at the same time in CIP communications 1.
TRUE: More than one data link start/stop switch changed to TRUE at the same time.
FALSE: Other than the above.
NJ-series CPU Units: Indicates that more than one switch turned ON at the same time
TRUE: More than one data link start/stop switch changed to TRUE at the same time.
FALSE: Other than the above.
Data type
BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
Variable name
_EIP1_MultiSwONErr
Meaning
CIP Communications1 Multiple Switches ON
Error
Global/local
Global
Function
Indicates that more than one switch turned ON at the same time in CIP communications 1.
TRUE: More than one data link start/stop switch changed to TRUE at the same time.
FALSE: Other than the above.
Note
You can use this system-defined variable only for NX-series CPU Units.
Data type
BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
Variable name
_EIP2_MultiSwONErr
Meaning
CIP Communications2 Multiple Switches ON
Error
Global/local
Global
Function
Indicates that more than one switch turned ON at the same time in CIP communications 2.
TRUE: More than one data link start/stop switch changed to TRUE at the same time.
FALSE: Other than the above.
Note
You can use this system-defined variable only for the NX701 CPU Units and NX102 CPU Units.
Data type
BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-50
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......