Level 1
Level 2
Level 3
Variable
Name
Variable
Name
Variable
Name
_EIP_ErrSta
Built-in Ether-
Net/IP Error
_EIP_Por-
tErr
Communi-
cations
Port Error
_EIP_MacAdrErr
MAC Address Error
_EIP_LanHwErr
Communications Controller Error
_EIP_EtnCfgErr
Basic Ethernet Setting Error
_EIP_IPAdrCfgErr
IP Address Setting Error
_EIP_IPAdrDupErr
IP Address Duplication Error
_EIP_BootpErr
BOOTP Server Error
_EIP_DNSSrvErr
DNS Server Connection Error
_EIP_IPRTblErr
IP Route Table Error
_EIP_Ci-
pErr
CIP Com-
munica-
tions Error
_EIP_IdentityErr
Identity Error
_EIP_TDLinkCfgErr
Tag Data Link Setting Error
_EIP_TDLinkOpnErr
Tag Data Link Connection Failed
_EIP_TDLinkErr
Tag Data Link Communications Er-
ror
_EIP_TagAdrErr
Tag Name Resolution Error
_EIP_MultiSwONErr
Multiple Switches ON Error
_EIP_Tcp
AppErr
TCP Ap-
plication
Communi-
cations
Error
_EIP_TcpAppCfgErr
TCP Application Setting Error
_EIP_NTPSrvErr
NTP Server Connection Error
Hierarchical Relationship of System-defined Variables Related to EtherNet/IP Errors in the
NX-series CPU Unit
The system-defined variables that are related to EtherNet/IP errors have the following hierarchical
relationship. For example, if the value of any of the
_EIP1_PortErr
,
_EIP2_PortErr
,
EIP1_CipErr
,
_EIP2_CipErr
, and
_EIP_TcpAppErr
variables in the second level is TRUE, then the
_EIP_ErrSta
variable in the first level also changes to TRUE. Therefore, you can check the values of system-
defined variables in a higher level to see if an error has occurred for a variable in a lower level.
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-19
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
3-2 System-defined V
ariables
3
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......