Variable name
_EIP_TargetPLCErr[255]
Meaning
Target PLC Error Information
Global/local
Global
Function
NX-series CPU Units: Shows the error status (logical OR of fatal and non-fatal errors) of the target node Control-
lers that are connected for CIP communications 1, with the built-in EtherNet/IP ports as the originator. The array
elements are valid only when the corresponding Normal Target Node Information is TRUE. The immediately pre-
ceding value is retained if this variable is FALSE.
Array[x] is TRUE: A fatal or non-fatal error occurred in the target Controller with a target node ID of x.
Array[x] is FALSE: Other than the above.
NJ-series CPU Units: Shows the error status (logical OR of fatal and non-fatal errors) of the target node Control-
lers that are connected with the built-in EtherNet/IP ports as the originator. The array elements are valid only
when the corresponding Normal Target Node Information is TRUE. The immediately preceding value is retained if
this variable is FALSE.
Array[x] is TRUE: A fatal or non-fatal error occurred in the target Controller with a target node ID of x.
Array[x] is FALSE: Other than the above.
Data type
ARRAY [0..255] OF BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
Variable name
_EIP1_TargetPLCErr[255]
Meaning
CIP Communications1 Target PLC Error Infor-
mation
Global/local
Global
Function
Shows the error status (logical OR of fatal and non-fatal errors) of the target node Controllers that are connected
for CIP communications 1, with the built-in EtherNet/IP ports as the originator. The array elements are valid only
when the corresponding Normal Target Node Information is TRUE. The immediately preceding value is retained if
this variable is FALSE.
Array[x] is TRUE: A fatal or non-fatal error occurred in the target Controller with a target node ID of x.
Array[x] is FALSE: Other than the above.
Note
You can use this system-defined variable only for NX-series CPU Units.
Data type
ARRAY [0..255] OF BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
Variable name
_EIP2_TargetPLCErr[255]
Meaning
CIP Communications2 Target PLC Error Infor-
mation
Global/local
Global
Function
Shows the error status (logical OR of fatal and non-fatal errors) of the target node Controllers that are connected
for CIP communications 2, with the built-in EtherNet/IP ports as the originator. The array elements are valid only
when the corresponding Normal Target Node Information is TRUE. The immediately preceding value is retained if
this variable is FALSE.
Array[x] is TRUE: A fatal or non-fatal error occurred in the target Controller with a target node ID of x.
Array[x] is FALSE: Other than the above.
Note
You can use this system-defined variable only for the NX701 CPU Units and NX102 CPU Units.
Data type
ARRAY [0..255] OF BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-57
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
3-3
Specifications for Individual System-defined V
aria-
bles
3
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......