Variable name
Meaning
Function
Data type
Range of
values
Reference
_EIP_TDLinkCfgErr
Tag Data Link Setting
Error
NX-series CPU Units: Indicates that the
tag data link settings for CIP communica-
tions 1 are incorrect. Or, a read operation
failed.
TRUE: Setting incorrect or read failed.
FALSE: Normal
NJ-series CPU Units: Indicates that the
tag data link settings are incorrect. Or, a
read operation failed.
TRUE: Setting incorrect or read failed.
FALSE: Normal
BOOL
TRUE or
FALSE
_EIP1_TDLinkCfgErr
CIP Communica-
tions1 Tag Data Link
Setting Error
Indicates that the tag data link settings
for CIP communications 1 are incorrect.
Or, a read operation failed.
TRUE: Setting incorrect or read failed.
FALSE: Normal
Note
You can use this system-de-
fined variable only for NX-ser-
ies CPU Units.
BOOL
TRUE or
FALSE
_EIP2_TDLinkCfgErr
CIP Communica-
tions2 Tag Data Link
Setting Error
Indicates that the tag data link settings
for CIP communications 2 are incorrect.
Or, a read operation failed.
TRUE: Setting incorrect or read failed.
FALSE: Normal
Note
You can use this system-de-
fined variable only for the
NX701 CPU Units and NX102
CPU Units.
BOOL
TRUE or
FALSE
_EIP_TDLinkOpnErr
Tag Data Link Con-
nection Failed
NX-series CPU Units: Indicates that es-
tablishing a tag data link connection for
CIP communications 1 failed.
TRUE: Establishing a tag data link con-
nection failed due to one of the following
causes.
•
The information registered for a target
node in the tag data link parameters is
different from the actual node informa-
tion.
•
There was no response from the re-
mote node.
FALSE: Other than the above.
NJ-series CPU Units: Indicates that es-
tablishing a tag data link connection
failed.
TRUE: Establishing a tag data link con-
nection failed due to one of the following
causes.
•
The information registered for a target
node in the tag data link parameters is
different from the actual node informa-
tion.
•
There was no response from the re-
mote node.
FALSE: Other than the above.
BOOL
TRUE or
FALSE
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-14
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......