Variable name
_EIP_MacAdrErr
Meaning
MAC Address Error
Global/local
Global
Function
NX-series CPU Units: Indicates that an error occurred when the MAC address was read on the communications
port 1 at startup.
TRUE: Error
FALSE: Normal
NJ-series CPU Units: Indicates that an error occurred when the MAC address was read at startup.
TRUE: Error
FALSE: Normal
Data type
BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
Variable name
_EIP1_MacAdrErr
Meaning
Port1 MAC Address Error
Global/local
Global
Function
Indicates that an error occurred when the MAC address was read on the communications port 1 at startup.
TRUE: Error
FALSE: Normal
Note
You can use this system-defined variable only for NX-series CPU Units.
Data type
BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
Variable name
_EIP2_MacAdrErr
Meaning
Port2 MAC Address Error
Global/local
Global
Function
Indicates that an error occurred when the MAC address was read on the communications port 2 at startup.
TRUE: Error
FALSE: Normal
Note
You can use this system-defined variable only for the NX701 CPU Units and NX102 CPU Units.
Data type
BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
Variable name
_EIP_LanHwErr
Meaning
Communications Controller Error
Global/local
Global
Function
NX-series CPU Units: Indicates that a communications controller failure occurred on the communications port 1.
TRUE: Failure
FALSE: Normal
NJ-series CPU Units: Indicates that a communications controller failure occurred.
TRUE: Failure
FALSE: Normal
Data type
BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-40
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......