Parameter name
Data type
Description
Reserved
UDINT
Reserved
Vendor code
UDINT
Vendor code
Device type code
UDINT
Device type code
Product code
UDINT
Product code of the Unit in which errors occurred
Additional information[0]
to
Additional information[31]
Array of BYTE
Attached information (system information) of event.
Reserved[0]
to
Reserved[23]
Array of BYTE
Reserved
NX Unit
Parameter name
Data type
Description
Index
UDINT
Current error index number
This number is assigned when system event logs
and access event logs are registered.
Unit number
USINT
Unit number
0000 hex: Controller
0001 to 0020 hex: NX Unit
Event priority
USINT
Error level
Event occurred time
UDINT
Error occurred time
Product code
UDINT
Product code of the Unit in which errors occurred
Event code
UDINT
Event code
Additional information[0]
to
Additional information[31]
Array of BYTE
Attached information (system information) of event.
CIP Error Codes
General sta-
tus code
(hex)
Error name
Cause
02
Resource unavailable
Resources needed for the object to perform the requested
service were unavailable.
0C
Object state conflict
The object cannot perform the requested service in its cur-
rent mode/state.
13
Not enough data
Data required for the execution of the required service is in-
sufficient.
15
Too much data
Extra data for the execution of the required service is includ-
ed.
1F
Vendor specific error
The service could not be executed due to internal reasons.
20
Invalid parameter
•
The Unit number is out of the supported range.
•
The specification of the number of readout records is out
of the range.
•
The Unit does not exist.
Method of Use
1
The following variables are generated and initialized to 0.
8 CIP Message Communications
8-61
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
8-5
CIP Object Services
8
8-5-3
NX Configuration Object (Class ID: 74 hex)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......