• Destination address: Specify the destination IP address
Route Path : 01\#01 \02\192.168.251.2
(a)
(b)
3. Communicating with the destination built-in EtherNet/IP port 2 (destination CPU #01) via the
destination built-in EtherNet/IP port 1 (destination CPU #00)
(Local CPU #00 to destination CPU #01 via destination CPU #00)
(a)
(b)
Communications
port (#02)
Communications
port (#02)
Communications
port (#02)
Communications
port (#02)
NX701 CPU Unit or NX102 CPU Unit
NX701 CPU Unit or NX102 CPU Unit
CPU#00
(Unit address 00 hex)
CPU#01
(Unit address 01 hex)
CPU#00
(Unit address 00 hex)
CPU#01
(Unit address 01 hex)
Backplane port
(#01)
Built-in EtherNet/IP
port 1
Built-in EtherNet/IP
port 2
Built-in EtherNet/IP
port 1
Built-in EtherNet/IP
port 2
IP address :
192.168.250.2
a) Local CPU #00 to destination IP address
• Network type number: "02" (Output to the communications port)
• Destination address: Specify the destination IP address
b) Destination backplane to destination CPU #01
• Network type number: "01" (Output to Backplane port)
• Destination address: "#01" (CPU#01)
Route Path : 02\192.168.250.2 \01\#01
(a)
(b)
4. Communicating with the destination built-in EtherNet/IP port 1 (destination CPU #00) via the
destination built-in EtherNet/IP port 2 (destination CPU #01)
(Local CPU #00 to destination CPU #00 via destination CPU #01)
(a)
(b)
(c)
Communications
port (#02)
Communications
port (#02)
Communications
port (#02)
Communications
port (#02)
Backplane port
(#01)
Backplane port
(#01)
NX701 CPU Unit or NX102 CPU Unit
NX701 CPU Unit or NX102 CPU Unit
CPU#00
(Unit address 00 hex)
CPU#01
(Unit address 01 hex)
CPU#00
(Unit address 00 hex)
CPU#01
(Unit address 01 hex)
Built-in EtherNet/IP
port 1
Built-in EtherNet/IP
port 2
Built-in EtherNet/IP
port 1
Built-in EtherNet/IP
port 2
IP address :
192.168.251.2
a) Local backplane to local CPU #01
• Network type number: "01" (Output to Backplane port)
• Destination address: "#01" (CPU#01) Note: This is in order to output using the sender IP
address of the built-in EtherNet/IP port 2.
8 CIP Message Communications
8-11
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
8-2 CIP Message Communications Client Function
8
8-2-4
Route Path
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......