background image

identiv.com  

  [email protected]  

  +1 888-809-8880

Input / Output (FB3) Freedom Bridge

 

Installation Guide

PART NUMBERS

50-40-I/O, 50-40-I/OL

Replaces 50-40-3

50-24-I/O

Replaces 50-24-3

PHYSICAL SPECIFICATIONS

Length

76 mm (3.00 in.)

Width

47 mm (1.85 in.)

Height

17 mm (0.67 in.)

Weight

34 g (1.20 oz.)

Max Readers

0

Max Input

12

Max Output

2

Certifications

Electrical:

 UL294 and UL294B 

Power over ethernet:

 IEEE 802af 

Mode A only, Class 2 (6.49 Watts)

EMI Radiation:

 FCC Part 15 Class B

SUMMARIZED LEVELS OF  

ACCESS CONTROL COMPONENTS

Destructive Attack

Level I

Line Security

Level I

Endurance

Level I

Standby Power

Level I

Single Point Locking

Level I

BASE PLATE MOUNTING

Dimension

Millimeters

Inches

A

116.07

4.57

B

78.74

3.10

C

15.24

0.60

D

85.59

3.37

E

10.16

0.40

F

58.42

2.30

E

D

A

C

B

F

Freedom Bridges should only be installed in dry, non-condensing 
environments. The ambient temperature of the environment should 
range between -40°C and 50°C.      

Freedom Encryption Bridges should only be mounted to non-conductive 
surfaces. Incorrect mounting may short-circuit the electronics, which will 
cause it to malfunction.

DC power, reader, input contact, and output device wires should 
be between 16-28 AWG. They should also be stripped 5.5mm to 
sufficiently fit the terminal blocks and ensure that they do not come in 
contact with each other.

INSTALLATION REQUIREMENTS

For each of the following steps, be sure to reference the wiring 

diagram on page 2 for additional details: 

1. 

If you have any supervised input contacts, wire them to the Digital 
Contact Inputs using Method 1 or Method 2. 

Note:

 Only In5, In6, 

In11, and In12 support Input Supervision. 

2. 

If you have any non-supervised input contacts, wire them to the 
Digital Contact Inputs. 

3. 

Wire the output devices to the Relay Outputs.

4. 

Supply power to the Freedom Bridge using either or both of the 
following methods:

A. 

A 2.25 – 5.25W Power over Ethernet (PoE) port on an 
Ethernet switch connected to the Freedom Bridge using 
a Cat5e or Cat6 cable. (Passive injectors not supported; 
Mode A PoE only)

B. 

12 – 16Vdc & 350mA (300mA external & 50 mA internal) 
DC power connected directly to the TB1 terminal on the 
Freedom Bridge.

5. 

If you are not using PoE to power your Freedom Bridge, connect 
a Cat5e or Cat6 cable from any port on an Ethernet Switch to 
the RJ-45 connector on the Freedom Bridge. 

Note:

 Ethernet only 

supports a maximum cable length of 100 m. 

6. 

To configure and add the Freedom Bridge to a MESH/Freedom 
Server, refer to the MESH/Freedom Solution Guide manual.

INSTALLATION PROCEDURE

Отзывы: