![Omron Sysmac NX1P2-10 1 Series User Manual Download Page 62](http://html1.mh-extra.com/html/omron/sysmac-nx1p2-10-1-series/sysmac-nx1p2-10-1-series_user-manual_1633435062.webp)
1-5
EtherNet/IP Communications Proce-
dures
Basic Operation
1
Wire the Ethernet network with twisted-pair cable.
Section 2 Installing Ethernet Net-
works
↓
2
Set the built-in EtherNet/IP port IP address with the Sysmac
Studio.
Section 4 Determining IP Ad-
dresses
1. Use the Sysmac Studio to create a new project.
2. Set the local IP address in one of the following ways:
•
Defaults:
NX701 CPU Unit
Built-in EtherNet/IP port 1
: 192.168.250.1
(subnet mask = 255.255.255.0)
Built-in EtherNet/IP port 2
: 192.168.251.1
(subnet mask = 255.255.255.0)
NX102 CPU Unit
Built-in EtherNet/IP port 1
: 192.168.250.1
(subnet mask = 255.255.255.0)
Built-in EtherNet/IP port 2
: 192.168.251.1
(subnet mask = 255.255.255.0)
NX1P2 CPU Unit Built-in EtherNet/IP port
: 192.168.250.1
(subnet mask = 255.255.255.0)
NJ-series CPU Unit Built-in EtherNet/IP port
•
Set any IP address.
•
Obtain from the BOOTP server.
↓
3
Perform a communications test with a PING command from a
computer.
Section 6 Testing Communica-
tions
↓
4
Use the Sysmac Studio to set the initial settings of the Ether-
Net/IP Function Module.
Section 5 Sysmac Studio Set-
tings for the Built-in EtherNet/IP
Port
•
Set the TCP/IP settings and Ethernet settings as required.
Using Tag Data Links
1
Import the variable settings for the tags that were created on
the Sysmac Studio to the Network Configurator.
7-2-4 Creating Tags and Tag Sets
↓
2
Use the Network Configurator to create the tag data link table.
Section 7 Tag Data Link Func-
tions
•
Create the network configuration.
•
Set the tags, tag sets, and connections.
↓
3
Connect the Network Configurator online.
↓
4
Download the tag data link setting.
↓
1 Introduction
1-28
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......