Chapter 10
10-58
Appendices
Note 1.
Values in parentheses are for 400-V-class Inverters.
Note 2.
The setting range is 10% to 200% of the Inverter's rated output current. The values for a 200-
V-class 0.4-kW Inverter are given above.
Note 3.
When the control mode is changed, the Inverter will revert to default settings. (The V/f control
default settings are given above.)
Note 4.
E1-13 will be the same value as E1-05 after autotuning.
Note 5.
The upper setting limit will be 150.0 Hz when C6-01 is set to 0.
Note 6.
The settings of E1-11 and E1-12 are ignored if set to 0.0.
Note 7.
If multi-function input H1-
@@
is set to 16 (motor 2), the default setting will depend upon the
Inverter capacity. The value for a 200-V-class 0.4-kW Inverter is given.
Note 8.
Values in parentheses are for Asian model Inverters.
■
Option Parameters
E4-03
0323
03
23
Motor 2 no-load current
0.00 to
1.89
(See
note 7.)
0.01 A
Depends
on
capacity.
No
E4-04
0324
03
24
Motor 2 number of poles (number of
poles)
2 to 48
1 pole
4
No
E4-05
0325
03
25
Motor 2 line-to-line resistance
0.000 to
65.000
0.01
Ω
Depends
on
capacity.
No
E4-06
0326
03
26
Motor 2 leak inductance
0.0 to
40.0
0.1%
Depends
on
capacity.
No
E4-07
0327
03
27
Motor 2 rated capacity
0.40 to
650.00
0.01 kW
Depends
on
capacity.
No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
F1-01
0380
03
80
PG constant
0 to
60000
1
1024
(600)
(See
note.)
No
F1-02
0381
03
81
Operation selection at PG open circuit
(PGO)
0 to 3
1
1
No
F1-03
0382
03
82
Operation selection at overspeed (OS)
0 to 3
1
1
No
F1-04
0383
03
83
Operation selection at deviation
0 to 3
1
3
No
F1-05
0384
03
84
PG rotation
0, 1
1
0
No
F1-06
0385
03
85
PG division rate (PG pulse monitor)
0 to 132
1
1
No
F1-07
0386
03
86
Integral value during accel/decel
enable/disable
0, 1
1
0
No
F1-08
0387
03
87
Overspeed detection level
0 to 120
1%
115
No
F1-09
0388
03
88
Overspeed detection delay time
0.0 to 2.0 0.1 s
1.0
No
F1-10
0389
03
89
Excessive speed deviation detection
level
0 to 50
1%
10
No
F1-11
038A
03
8A
Excessive speed deviation detection
delay time
0.0 to
10.0
0.1 s
0.5
No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...