Chapter 10
10-91
Appendices
Note 1.
Maximum (upper limit) temperature was exceeded.
Note 2.
Set temperature was exceeded.
10-7-3 Parameter Reading and Writing
The following tables show the SYSDRIVE 3G3FV Inverter parameters and the corresponding regis-
ter numbers. Write and read the various parameters with “1" as the minimum setting unit. Negative
numbers are expressed as two's complement. If the setting unit is in hexadecimal, there is no need to
convert it.
When writing data in parameters, be sure to send an enter command to enable the written data.
Unless the enter command is transmitted, the data will not be enabled and the Inverter may not start.
■
Parameters for Initialize Mode
14
EF6
External fault (Terminal 6)
15
EF7
External fault (Terminal 7)
16
EF8
External fault (Terminal 8)
17
---
Not used.
18
OS
Overspeed
19
DEV
Speed deviation
1A
PGO
PG is disconnected
1B
PF
Input phase loss
1C
LF
Output phase loss
1D
---
Not used.
1E
OPR
OPR disconnected
1F
ERR
EEPROM error
21 to FF
---
Not used.
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
A1-00
0100
---
---
Display Language
0 to 6
1
1
Yes
A1-01
0101
01
01
Access Level
0 to 4
1
2
Yes
A1-02
0102
01
02
Select Control Method
0 to 3
1
2
No
A1-03
0103
---
---
Initialize
0 to 3330 1
0
No
A1-04
0104
---
---
Password
0 to 9999 1
0
No
A1-05
0105
---
---
Setting the Password
0 to 9999 1
0
No
A2-01
to
A2-32
0106 to
0125
---
---
User-parameter settings
0180 to
050C
Set the
register
numbers
for b1-01
to o2-08.
---
---
No
Code
Display
Content
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...